Skip to search boxSkip to navigationSkip to main content

Verification of lifetime arching stress withstand of circuit breakers through testing

Output:
Chapter in Book/Report/Conference proceeding
Conference contribution
Academic
Peer-review

Information

Output type

Output:
Chapter in Book/Report/Conference proceeding
Conference contribution
Academic
Peer-review

Original language

English

Pages from-to (Number of pages)

Pages 1-6

Publication milestones

  • Published - 2009

Publication status

Published - 2009

Place of publication

Paris

Publisher

CIGRE

Host publication title

Proceedings of the 6th Southern Africa Regional Conference, CIGRE, 17-21 August 2009, Capetown, South Africa

Abstract

This contribution quantifies the accumulated arcing stress inside high-voltage circuit breakers during a 25 year period of operation. Ageing mechanisms due to this arcing stress are discussed briefly. The aim is to design a suitable test program to verify endurance against this accumulated arcing stress: electrical endurance. Passing this test program should assure a period of 25 years without major maintenance. Data of fault- and network characteristics collected worldwide are used in a statistical computer model in order to quantify a realistic electrical endurance test program in a recently (2008) revised IEC standard. The actual standardisation status is outlined and discussed, and includes the situation for medium voltage breakers