Verification of lifetime arching stress withstand of circuit breakers through testing
- R.P.P. Smeets,
- P. Knol
Output:
Chapter in Book/Report/Conference proceeding
Conference contribution
Academic
Peer-reviewInformation
Output type
Output:
Chapter in Book/Report/Conference proceeding
Conference contribution
Academic
Peer-reviewOriginal language
EnglishPages from-to (Number of pages)
Pages 1-6Publication milestones
- Published - 2009
Publication status
Published - 2009
Place of publication
ParisPublisher
CIGREHost publication title
Proceedings of the 6th Southern Africa Regional Conference, CIGRE, 17-21 August 2009, Capetown, South AfricaAbstract
This contribution quantifies the accumulated arcing stress inside high-voltage circuit breakers during a 25 year period of operation. Ageing mechanisms due to this arcing stress are discussed briefly.
The aim is to design a suitable test program to verify endurance against this accumulated arcing stress: electrical endurance. Passing this test program should assure a period of 25 years without major maintenance.
Data of fault- and network characteristics collected worldwide are used in a statistical computer model in order to quantify a realistic electrical endurance test program in a recently (2008) revised IEC standard. The actual standardisation status is outlined and discussed, and includes the situation for medium voltage breakers