Verification of a Capacitive Voltage Divider With 6-μrad Uncertainty Up To 100 kV

  • Gu Ye(Corresponding author)
    ,
  • Wei Zhao(Corresponding author)
    ,
  • Gert Rietveld(Corresponding author)
Output:
Contribution to journal
Article
Academic
Peer-review

Open access

Information

Output type

Output:
Contribution to journal
Article
Academic
Peer-review

Original language

English

Article number

9353488

Pages from-to (Number of pages)

Pages 1-9 (9 pages)

Journal (Volume, Issue Number)

IEEE Transactions on Instrumentation and Measurement (Volume 70)

Publication milestones

  • Published - 11/02/2021

Publication status

Published - 11/02/2021

ISSN

0018-9456

Abstract

A reference setup for system calibration of industrial transformer loss measurement (TLM) systems consists of three main components, a voltage divider, a current transformer, and a power meter, and their phase displacements should each not be more than 10 μrad to achieve an overall system uncertainty of better than 20 μW/VA. We have extensively verified the uncertainty level of the current-comparator-based capacitive voltage divider (CVD) used in the TLM reference setup of the Van Swinden Laboratorium (VSL), both from the component level and the system as a whole. Different practical conditions relevant for on-site measurements are considered, e.g., measurement cable lengths, cable types, and grounding. The verification measurement results show an agreement of better than (6 ± 6) × 10 -6 in ratio error and (4 ± 6) μrad in phase displacement between the CVD component and system calibrations up to 100 kV. Requirements for achieving this agreement are adequate grounding of the CVD and the use of triax cable between the high-voltage (HV) capacitor and the CVD low-voltage electronics in case large distances have to be covered on-site. The (4±6) μrad agreement in phase displacement is well within the required 10 μrad limit for voltage measurements as part of on-site TLM system calibrations with 20 μW/VA overall uncertainty at low power factors.

Metrics

Metrics

Scopus
citations
1
SciVal
citations
1
SciVal
FWCI
0.08
SciVal
Author count
3
SciVal
Paper percentile
24
Download statistics
Download count
70

PlumX, opens in new tab

Captures
4
Citation count
1