Dynamic setpoint control for museum indoor climate conditioning integrating collection and comfort requirements: Development and energy impact for Europe.
- ,
- A.W.M. van Schijndel,
- H.L. Schellen
Output:
Contribution to journal
Article
Academic
Peer-reviewOpen access
Information
Output type
Output:
Contribution to journal
Article
Academic
Peer-reviewOriginal language
EnglishPages from-to (Number of pages)
Pages 14-31 (18 pages)Journal (Volume, Issue Number)
Building and Environment (Volume 118)Publication milestones
- Published - 01/06/2017
Publication status
Published - 01/06/2017
ISSN
0360-1323Abstract
This study presents a seven-step algorithm for hourly setpoint calculation of museums' indoor temperature (Ti) and relative humidity (RHi) integrating collection requirements (ASHRAE) and thermal comfort requirements. Moreover, building energy simulation results provide insight into the energy impact of five levels of museum indoor climate conditioning applied to four building quality levels (ranging from a historical building to a purpose-built museum building) using weather data from twenty locations throughout Europe. The five levels of indoor climate conditioning were calculated using the presented setpoint algorithm, a validated simulation model of museum Hermitage Amsterdam was adjusted to represent the four building quality levels, and technical-reference-year (TRY) weather data of twenty locations were used. The conclusions: The setpoint algorithm enables smooth control of seasonal adjustments, integrated with permissible short fluctuations of T and RH (according to ASHRAE classes); improving the building quality quickly follows the law of diminishing returns; supposing to result in the same collection risk, subclass Ad (no seasonal adjustments, but larger hourly fluctuations) is more energy efficient than subclass As (with seasonal adjustments, but smaller hourly fluctuations) for most locations; although class AA is more stringent than subclass As, class AA appears to require less energy than subclass As for some locations, due to efficiency differences of the humidification and dehumidification processes.
Documents and Links
Metrics
Metrics
SciVal
FWCI
2.37
SciVal
Author count
3
SciVal
Paper percentile
90
SciVal
citations
58
SciVal
Top percentile
10
Scopus
citations
59
Download statistics
Download count
433
PlumX, opens in new tab
Citation count
58
Captures
93