Power cable joint modelin high frequency

Yan Li, Peter A A F Wouters, Paul Wagenaars, Peter C.J.M. van der Wielen, E. Fred Steennis

Onderzoeksoutput: Hoofdstuk in Boek/Rapport/CongresprocedureConferentiebijdrageAcademicpeer review

4 Citaten (Scopus)

Samenvatting

Models in high frequency range for underground power cabling system are the basis for the analysis of many condition diagnostic techniques, for instance, partial discharge (PD) monitoring. This paper focuses on modeling of power cable joints. A cascaded transmission line model is proposed for 10kV oil-filled PILC-PILC straight power cable joint in thefrequency range of 300 kHz-800 MHz. It can be applied to interpret PD signal transmission and reflection behavior in power cable connections. The model is verified by S-parameter measurement.

Originele taal-2Engels
Titel2012 IEEE International Conference on Condition Monitoring and Diagnosis, CMD 2012
Plaats van productiePiscataway
UitgeverijInstitute of Electrical and Electronics Engineers
Pagina's76-79
Aantal pagina's4
ISBN van elektronische versie978-1-4673-1020-8
ISBN van geprinte versie978-1-4673-1019-2
DOI's
StatusGepubliceerd - 1 dec. 2012
Evenement2012 International Conference on Condition Monitoring and Diagnosis, CMD 2012 - Bali, Indonesië
Duur: 23 sep. 201227 sep. 2012

Congres

Congres2012 International Conference on Condition Monitoring and Diagnosis, CMD 2012
Land/RegioIndonesië
StadBali
Periode23/09/1227/09/12

Vingerafdruk

Duik in de onderzoeksthema's van 'Power cable joint modelin high frequency'. Samen vormen ze een unieke vingerafdruk.

Citeer dit