Samenvatting
This paper proposes a method for fault location in medium voltage grids with underground cables, using Bayesian inference. The prior distribution of fault position is obtained from the component failure database. With the measured fault loop impedance, the posterior distribution is calculated based on Bayes' theorem. Several random factors are considered during the calculation, including measurement errors, fault breakdown resistance, and inaccuracies of zero-sequence parameters. The distribution grid operators can use the calculated posterior distribution to rank the possible faulted sections and facilitate the restoration process, which can reduce the interruption duration of power supply.
| Originele taal-2 | Engels |
|---|---|
| Titel | Proceedings of PowerTech, 2015 IEEE Eindhoven, June 29 2015-July 2 2015, Eindhoven, The Netherlands |
| Plaats van productie | Piscataway |
| Uitgeverij | Institute of Electrical and Electronics Engineers |
| Pagina's | 1-5 |
| Aantal pagina's | 5 |
| DOI's | |
| Status | Gepubliceerd - 2 jul. 2015 |
| Evenement | 2015 IEEE Power Tech - Eindhoven, Nederland Duur: 29 jun. 2015 → 2 jul. 2015 http://powertech2015-eindhoven.tue.nl/ |
Congres
| Congres | 2015 IEEE Power Tech |
|---|---|
| Land/Regio | Nederland |
| Stad | Eindhoven |
| Periode | 29/06/15 → 2/07/15 |
| Ander | Towards Future Power Systems and Emerging Technologies |