This paper proposes a method for fault location in medium voltage grids with underground cables, using Bayesian inference. The prior distribution of fault position is obtained from the component failure database. With the measured fault loop impedance, the posterior distribution is calculated based on Bayes' theorem. Several random factors are considered during the calculation, including measurement errors, fault breakdown resistance, and inaccuracies of zero-sequence parameters. The distribution grid operators can use the calculated posterior distribution to rank the possible faulted sections and facilitate the restoration process, which can reduce the interruption duration of power supply.
Originele taal-2Engels
TitelProceedings of PowerTech, 2015 IEEE Eindhoven, June 29 2015-July 2 2015, Eindhoven, The Netherlands
Plaats van productiePiscataway
UitgeverijInstitute of Electrical and Electronics Engineers
Pagina's1-5
Aantal pagina's5
DOI's
StatusGepubliceerd - 2 jul 2015
Evenement2015 IEEE Power Tech - Eindhoven, Nederland
Duur: 29 jun 20152 jul 2015
http://powertech2015-eindhoven.tue.nl/

Congres

Congres2015 IEEE Power Tech
Land/RegioNederland
StadEindhoven
Periode29/06/152/07/15
AnderTowards Future Power Systems and Emerging Technologies