Samenvatting
We model power grids as graphs with heavy-tailed sinks, which represent demand from cities, and study cascading failures on such graphs. Our analysis links the scale-free nature of blackout sizes to the scale-free nature of city sizes, contrasting previous studies suggesting that this nature is governed by self-organized criticality. Our results are based on a new mathematical framework combining the physics of power flow with rare event analysis for heavy-tailed distributions, and are validated using various synthetic networks and the German transmission grid.
Originele taal-2 | Engels |
---|---|
Artikelnummer | 058301 |
Aantal pagina's | 6 |
Tijdschrift | Physical Review Letters |
Volume | 125 |
Nummer van het tijdschrift | 5 |
DOI's | |