Interference voltages can be reduced to an arbitrarily low level by careful design of the lay-out. Different types of cabling have been compared in a 150 kV substation. An interference level of less than 1 V was obtained by a shielded cable in an iron conduit; without any attention to the cabling, a level of 2.3 kV was measured