Samenvatting
Small capacitive current interruption with air-break disconnectors in a high-voltage network is an interactive event between circuit and arc with multiple re-ignitions during opening.
In order to investigate the transient phenomena, a set-up to measure arc characteristics is
developed and a series of interruption tests is performed. The system voltage is up to 150kV rms and the interruption capacitive current is up to 0.35A rms. The voltages across load- and sourceside capacitances and the current through the disconnector are recorded. Based on test data, arc characteristics such as arc conductance, arc power and v-i characteristic are studied. A comparison between the test and simulation shows good agreement.
Originele taal-2 | Engels |
---|---|
Titel | Proceedings of the 16th international symposium on High voltage engineering, Cape Town, South Africa, 24-28 August, 2009 |
Plaats van productie | Johannesburg |
Uitgeverij | SAIEE |
Pagina's | G-19-1/6 |
ISBN van geprinte versie | 978-0-620-44584-9 |
Status | Gepubliceerd - 2009 |