This paper proposes an impedance-based analytical method for modeling and estimation of harmonic interactions between the grid and DG inverters. The root cause of harmonic interaction/resonance problems is introduced. Starting with a simple PI regulator controlled inverter, the output impedance of the converter is modeled and proven by simulations to be operative for forecasting harmonic interactions. Moreover, another test case based on an inverter with multiple PR controllers is designed and modeled to clarify impedance-based design and harmonic interaction analysis. Assuming the impedance models of individual inverters and local loads within a distribution grid are knowledgeable, especially in the case of new grids under construction, harmonic interactions between the grid and a certain number of DG inverters can be preliminarily estimated.
Originele taal-2Engels
TitelProceedings of the IEEE International Energy Conference and Exhibition (EnergyCon), 18-22 December 2010
Plaats van productiePiscataway
UitgeverijInstitute of Electrical and Electronics Engineers
Pagina's194-199
Aantal pagina's6
ISBN van elektronische versie978-1-4244-9380-7
ISBN van geprinte versie978-1-4244-9378-4
DOI's
StatusGepubliceerd - 2010
Evenement2010 IEEE International Energy Conference - Manama, Bahrain, Manama, Bahrein
Duur: 18 dec. 201022 dec. 2010

Congres

Congres2010 IEEE International Energy Conference
Land/RegioBahrein
StadManama
Periode18/12/1022/12/10

Vingerafdruk

Duik in de onderzoeksthema's van 'Analysis of harmonic interactions between DG inverters and polluted grids'. Samen vormen ze een unieke vingerafdruk.

Citeer dit