Samenvatting
An analysis of current transients caused by voltage notches in an industrial plant is presented in the paper. The source of current transients in the factory lighting was traced to the operation of the nearby six-pulse AC/DC converter. Because of the short duration of the phenomenon, it was not possible to determine if there is a parallel resonance using a standard power quality analyzer. To determine the nature of the interaction, a measurement was done with a storage oscilloscope, and advanced signal processing was applied to the results. Using this technique, it was possible to exclude the presence of a parallel resonance. It was concluded that the transients are a reaction of lamps to voltage notches in certain working regimes of the six-pulse converter. Possible solutions to the problem are separating the supplies of the converter and the lighting installation, filtering, or adding additional line reactances.
| Originele taal-2 | Engels |
|---|---|
| Titel | Proceedings of the IEEE Power and Energy Society General Meeting 2011 (IEEE PES GM 2011), 24-29 July 2011, Detroit USA, |
| Plaats van productie | Piscataway |
| Uitgeverij | Institute of Electrical and Electronics Engineers |
| Pagina's | 1-7 |
| ISBN van geprinte versie | 978-1-4577-1001-8 |
| DOI's | |
| Status | Gepubliceerd - 2011 |
| Evenement | 2011 IEEE Power and Energy Society General Meeting (PESGM 2011) - Renaissance Center, Detroit, Verenigde Staten van Amerika Duur: 24 jul. 2011 → 28 jul. 2011 http://www.pes-gm.org/2011/ |
Congres
| Congres | 2011 IEEE Power and Energy Society General Meeting (PESGM 2011) |
|---|---|
| Land/Regio | Verenigde Staten van Amerika |
| Stad | Detroit |
| Periode | 24/07/11 → 28/07/11 |
| Ander | 2011 IEEE PES General Meeting, San Diego, USA |
| Internet adres |