Analysis of current transients caused by voltage notches

V. Cuk, J.F.G. Cobben, W.L. Kling, R.B. Timens

Onderzoeksoutput: Hoofdstuk in Boek/Rapport/CongresprocedureConferentiebijdrageAcademic

Samenvatting

An analysis of current transients caused by voltage notches in an industrial plant is presented in the paper. The source of current transients in the factory lighting was traced to the operation of the nearby six-pulse AC/DC converter. Because of the short duration of the phenomenon, it was not possible to determine if there is a parallel resonance using a standard power quality analyzer. To determine the nature of the interaction, a measurement was done with a storage oscilloscope, and advanced signal processing was applied to the results. Using this technique, it was possible to exclude the presence of a parallel resonance. It was concluded that the transients are a reaction of lamps to voltage notches in certain working regimes of the six-pulse converter. Possible solutions to the problem are separating the supplies of the converter and the lighting installation, filtering, or adding additional line reactances.
Originele taal-2Engels
TitelProceedings of the IEEE Power and Energy Society General Meeting 2011 (IEEE PES GM 2011), 24-29 July 2011, Detroit USA,
Plaats van productiePiscataway
UitgeverijInstitute of Electrical and Electronics Engineers
Pagina's1-7
ISBN van geprinte versie978-1-4577-1001-8
DOI's
StatusGepubliceerd - 2011
Evenement2011 IEEE Power and Energy Society  General Meeting (PESGM 2011) - Renaissance Center, Detroit, Verenigde Staten van Amerika
Duur: 24 jul 201128 jul 2011
http://www.pes-gm.org/2011/

Congres

Congres2011 IEEE Power and Energy Society  General Meeting (PESGM 2011)
LandVerenigde Staten van Amerika
StadDetroit
Periode24/07/1128/07/11
Ander2011 IEEE PES General Meeting, San Diego, USA
Internet adres

Vingerafdruk Duik in de onderzoeksthema's van 'Analysis of current transients caused by voltage notches'. Samen vormen ze een unieke vingerafdruk.

Citeer dit