Abstract

This contribution quantifies the accumulated arcing stress inside high-voltage circuit breakers during a 25 year period of operation. Ageing mechanisms due to this arcing stress are discussed briefly. The aim is to design a suitable test program to verify endurance against this accumulated arcing stress: electrical endurance. Passing this test program should assure a period of 25 years without major maintenance. Data of fault- and network characteristics collected worldwide are used in a statistical computer model in order to quantify a realistic electrical endurance test program in a recently (2008) revised IEC standard. The actual standardisation status is outlined and discussed, and includes the situation for medium voltage breakers
Original languageEnglish
Title of host publicationProceedings of the 6th Southern Africa Regional Conference, CIGRE, 17-21 August 2009, Capetown, South Africa
Place of PublicationParis
PublisherCIGRE
Pages1-6
Publication statusPublished - 2009

Fingerprint Dive into the research topics of 'Verification of lifetime arching stress withstand of circuit breakers through testing'. Together they form a unique fingerprint.