The striking role of partial valve stroke testing to meet safety integrity levels

B. Knegtering, J.L. Rouvroye

    Research output: Contribution to journalArticleAcademicpeer-review

    Abstract

    Partial Valve Stroke Testing or PVST, is an emerging concept to automatically increase the performance of Safety Instrumented Systems. PVST is a concept where safety-related valves like ESD valves and shut-off valves are automatically tested concerning failure modes that are related to valve sticking and slowing down operation. Current trends in the industry show an upcoming number of dedicated technical PVST solutions by various automation and instrumentation vendors. This paper will discuss practical examples of Partial Valve Stroke Testing in which it appears that SIL 1 rated valves can be upgraded to SIL 2, and off-line proof test intervals which can be extended from 2 to 5 years.
    Original languageEnglish
    Pages (from-to)16-21
    Number of pages6
    JournalRAMS Asia
    Volume2
    Issue number1
    Publication statusPublished - 2007