Simulace chladicího systému datacentra v havarijním stavu

Translated title of the contribution: Simulation of a data center cooling system in emergency situation

V. Zavrel, M. Barták, J.L.M. Hensen

Research output: Contribution to journalArticleProfessional

1 Citation (Scopus)

Abstract

The paper deals with the simula tion of indoor environment in a da ta center a t breakdown of its cooling sys - tem. Individual components of the cooling system during the breakdown were studied in detail with respect to their influence on the course of the emergency situation, in particular the influence of the cooling circuit thermal capacity. A complex numerical model was set up in TRNSYS simulation environment to predict energy flows and air temperatures in the data center. The simulation model describes in detail the cooling system including control elements and it takes into account heat accumulation in room constructions. The model represents a real data center and it was calibrated using data from a real emergency situation. The simulation results showed that the backup of water circuit makes possible to extend the operation time of the data center at emergency.

Translated title of the contributionSimulation of a data center cooling system in emergency situation
Original languageCzech
Pages (from-to)155-159
Number of pages5
JournalVytápeni, Vetrání, Instalace ; VVI
Volume24
Issue number4
Publication statusPublished - 1 Sept 2015