Safety Aspects of GSM Systems on High-Voltage Towers: An Experimental Analysis

J.B.M. Waes, van, A.P.J. Deursen, van, M.J.M. van Riet, F. Provoost

Research output: Contribution to journalArticleAcademicpeer-review

10 Citations (Scopus)
1 Downloads (Pure)

Abstract

Low-voltage (LV) applications mounted on high-voltage (HV) towers may pose a safety problem in the low voltage network when a flashover occurs over the high-voltage insulators. To study the effects experimentally, a 150 kV system was made available. On a high voltage tower carrying a cellular phone base station, one phase insulator was shorted to the tower. A current of about 200 A was injected into that phase at a large distance. We measured the current distribution and the relevant voltages in the low voltage net. The experimental current data agree with EMTP calculations. Appropriate measures to guarantee safety for persons and electronic equipment are discussed
Original languageEnglish
Pages (from-to)550-554
Number of pages5
JournalIEEE Transactions on Power Delivery
Volume17
Issue number2
DOIs
Publication statusPublished - 2002