Abstract
Abstract— Voltage dips constitute to a noticeable part of power
quality (PQ) problems but causing major financial losses to
industrial and commercial customers. This work involves
comparative studies to choose the most appropriate location of
monitoring dips for regulation. In this paper, a Dutch MV
network is used and dip monitoring locations are considered at
different points of connections (POC) where customers are
connected. To estimate the number of dips per year, simulations
are performed on the network using PowerFactory. The voltage
dip profiles at the selected monitoring point are analyzed for
phase and line voltage dips. The effects of distributed generation
(DG) on the voltage dips are also observed and the transfer of
voltage dips from MV to LV network is briefly discussed. To
analyze the effects of the expected dips on industrial equipment,
severity curves are applied onto the standard dip tables.
| Original language | English |
|---|---|
| Title of host publication | 16th IEEE International Conference on Harmonics and Quality of Power (ICHQP), 25-28 May 2014, Bucharest, Romania |
| Place of Publication | Bucharest, Romania |
| Publisher | Institute of Electrical and Electronics Engineers |
| Pages | 526-530 |
| ISBN (Print) | 978-1-4673-6487-4 |
| DOIs | |
| Publication status | Published - 2014 |
| Event | 16th International Conference on Harmonics and Quality of Power, ICHQP 2014 - Bucharest, Romania Duration: 25 May 2014 → 28 May 2014 Conference number: 16 |
Conference
| Conference | 16th International Conference on Harmonics and Quality of Power, ICHQP 2014 |
|---|---|
| Abbreviated title | ICHQP 2014 |
| Country/Territory | Romania |
| City | Bucharest |
| Period | 25/05/14 → 28/05/14 |