Abstract
This paper investigates the mechanism behind the 2nd harmonic interaction of a transformer connected Voltage-Source Converter (VSC) under saturation conditions. The detail small-signal models of a saturated transformer and a VSC are derived considering their nonlinear behavior. It is revealed that the frequency coupling from the saturated transformer and the PLL in the VSC may form a positive feedback loop and give rise to a 2nd harmonic amplification. The harmonic amplification gain is established herein, which provides an accurate assessment of the 2nd harmonic interaction. This theoretical analysis is verified by a power hardware in the loop laboratory experiment.
Original language | English |
---|---|
Title of host publication | 2018 IEEE International Power Electronics and Application Conference and Exposition (PEAC) |
Publisher | Institute of Electrical and Electronics Engineers |
Pages | 1-6 |
Number of pages | 6 |
ISBN (Electronic) | 978-1-5386-6054-6 |
DOIs | |
Publication status | Published - 27 Dec 2018 |
Externally published | Yes |
Keywords
- Harmonic interaction
- PLL
- VSC
- frequency coupling
- transformer core saturation