Abstract
In online single-sided partial discharge (PD) location settings, PD reflection patterns are affected by all components present in the cable circuit. This paper describes the performance of electromagnetic time reversal (EMTR) when interfering reflections contribute to the transient waveforms emitted by the PD. The analysed situation refers to a ring main unit (RMU) in the medium voltage (MV) grid where PD recordings are disturbed by signals reflected from the other cables connected to the RMU, potentially affecting the PD location accuracy. We show that the accuracy of EMTR-based location methods is unaffected by such effects.
| Original language | English |
|---|---|
| Number of pages | 2 |
| Publication status | Published - 2022 |
| Event | 11th International Conference on Computation in Electromagnetics, CEM 2023 - Cannes, France Duration: 11 Apr 2023 → 14 Apr 2023 Conference number: 11 |
Conference
| Conference | 11th International Conference on Computation in Electromagnetics, CEM 2023 |
|---|---|
| Abbreviated title | CEM 2023 |
| Country/Territory | France |
| City | Cannes |
| Period | 11/04/23 → 14/04/23 |