Electromagnetic time reversal applied to online partial discharge location in power cables: influence of interfering reflections from the cable circuit

Research output: Contribution to conferencePaperAcademic

Abstract

In online single-sided partial discharge (PD) location settings, PD reflection patterns are affected by all components present in the cable circuit. This paper describes the performance of electromagnetic time reversal (EMTR) when interfering reflections contribute to the transient waveforms emitted by the PD. The analysed situation refers to a ring main unit (RMU) in the medium voltage (MV) grid where PD recordings are disturbed by signals reflected from the other cables connected to the RMU, potentially affecting the PD location accuracy. We show that the accuracy of EMTR-based location methods is unaffected by such effects.
Original languageEnglish
Number of pages2
Publication statusPublished - 2022
Event11th International Conference on Computation in Electromagnetics, CEM 2023 - Cannes, France
Duration: 11 Apr 202314 Apr 2023
Conference number: 11

Conference

Conference11th International Conference on Computation in Electromagnetics, CEM 2023
Abbreviated titleCEM 2023
Country/TerritoryFrance
CityCannes
Period11/04/2314/04/23

Fingerprint

Dive into the research topics of 'Electromagnetic time reversal applied to online partial discharge location in power cables: influence of interfering reflections from the cable circuit'. Together they form a unique fingerprint.