Electro-optic voltage sensor based on BGO for air-insulated high voltage substations

S.V. Marchese, K. Bohnert, S. Wildermuth, J.L.M. van Mechelen, O. Steiger, L.C. Rodoni, G. Eriksson, J. Czyzewski

Research output: Chapter in Book/Report/Conference proceedingConference contributionAcademicpeer-review

7 Citations (SciVal)

Abstract

We present an electro-optic voltage sensor using bismuth germanate in a novel oil- and gas-free insulator. The performance is verified under varying external conditions. Accuracy within ±0.2% between -40 °C and +80°C is demonstrated.

Original languageEnglish
Title of host publication2013 IEEE Photonics Conference, IPC 2013
Pages608-609
Number of pages2
DOIs
Publication statusPublished - 2013
Externally publishedYes
Event26th IEEE Photonics Conference, IPC 2013 - Bellevue, United States
Duration: 8 Sept 201312 Sept 2013
Conference number: 26

Conference

Conference26th IEEE Photonics Conference, IPC 2013
Abbreviated titleIPC 2013
Country/TerritoryUnited States
CityBellevue
Period8/09/1312/09/13

Fingerprint

Dive into the research topics of 'Electro-optic voltage sensor based on BGO for air-insulated high voltage substations'. Together they form a unique fingerprint.

Cite this