Abstract
This study proposes a method for the determination of flicker contribution based on synchronised measurements of root mean square (RMS) voltages and currents. The advantage of this approach is the avoidance of time aggregation which is present in the analysis based on the short- or long-term flicker coefficient. The applicability of the method is demonstrated using phasor measurement unit measurements from a 50 kV network and compared with the results of an analysis based on instantaneous flicker coefficients.