Abstract
Three-phase three-wire shunt active power filter (SAPF) with traditional positive-sequence control can only compensate part of the nonlinear load current harmonics if the PCC voltage changes from balanced to unbalanced condition. Changes of both nonlinear load current harmonic components and equivalent circuit for modular multilevel converter based SAPF (MMC-SAPF) are analyzed in the paper. To solve the problems caused by PCC voltage switches between balanced and unbalanced conditions while MMC-SAPF operating, an adaptive control strategy for MMC-SAPF including the voltage unbalance detection and smoothly switching control on enabling/disabling the negative-sequence strategy is proposed. Simulation and experimental tests validate the effectiveness of the proposed control scheme on a downscaled 64V/2kVA apparatus.
| Original language | English |
|---|---|
| Title of host publication | IECON 2017 - 43rd Annual Conference of the IEEE Industrial Electronics Society |
| Publisher | Institute of Electrical and Electronics Engineers |
| Pages | 67-72 |
| ISBN (Electronic) | 978-1-5386-1127-2 |
| DOIs | |
| Publication status | Published - 2017 |
| Externally published | Yes |
Keywords
- Modular nudtilevel converter
- active power filter
- unbalanced PCC voltage
- nonlinear load
- multiple synchronous reference frame
Fingerprint
Dive into the research topics of 'Adaptive control for MMC-SAPF with balanced and unbalanced PCC voltage'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver